GE
12-Point Analog Current Output Module IC200ALG328 GE
In stock, ready to ship
Manufacturer: GE
Product No.: IC200ALG328
Product Type: VersaMax 12-Channel Analog Current Output Module
Product Origin: USA
Payment: T/T
Weight: 1400g
Shipping port: Xiamen
Warranty: 12 months
Yes, we provide a 30-day money-back guarantee for all purchases.
Yes, all items come with a 12-month warranty from the date of shipment.
Product Overview
The GE Fanuc IC200ALG328 is a 12-channel analog current output module for the VersaMax automation platform. It provides current signals to field devices such as control valves, positioners, and other process actuators. The module supports selectable 4–20 mA and 0–20 mA output ranges and requires an external DC supply for field-side output circuits.
Key Specs
- Product family: VersaMax
- Module type: Analog current output
- Number of channels: 12 single-ended outputs
- Resolution: 13-bit
- Output ranges: 4–20 mA default or 0–20 mA
- Output range selection: Jumper configuration
- Maximum resistive load: 800 ohms
- Maximum capacitive load: 0.1 µF
- Maximum inductive load: 0.5 H
- Output update rate: 15 ms maximum
- Accuracy at 25°C: ±0.3% typical, ±0.5% maximum of full scale
- Accuracy over 0–60°C: ±1% maximum of full scale
- External field power: 18–30V DC
- Field power consumption: 270 mA maximum with all 12 outputs at full scale
- Backplane current consumption: 50 mA maximum at 5V
- Output default: Hold Last State or configurable low-end-of-range behavior
Why Choose This
- Twelve current output channels support multiple analog control loops.
- Selectable output ranges accommodate 4–20 mA and 0–20 mA field devices.
- Jumper configuration allows selection of output behavior after loss of backplane power or communication.
- External field power supports the current output circuits.
- Field power diagnostics help identify supply interruptions.
Common Questions
What is the default output range?
The default range is 4–20 mA. A jumper can configure the module for 0–20 mA operation.
Does this module need external power?
Yes. The field-side output circuits require an external 18–30V DC supply.
What happens if backplane communication is interrupted?
The output behavior can be configured for Hold Last State or low-end-of-range operation. The external field supply must remain available for the output circuits.
Mounting Steps
- Install the module on a compatible VersaMax I/O carrier.
- Connect the external 18–30V DC field power supply.
- Set the output range and default behavior using the specified jumper configuration.
- Wire the 12 current output channels to the corresponding field devices.
- Configure the output channels in the PLC and verify current readings under operating conditions.
Buying Advice
Confirm the required current range, external supply capacity, output load resistance, and field wiring before ordering. Check the thermal derating requirements when operating multiple channels at high output levels. Do not confuse IC200ALG328 with IC200ALG327, which is a 12-channel voltage output module.