Industrial Ethernet | PROFINET Network Availability
A PROFINET ring can provide an alternative communication path when a network connection is interrupted. However, physically connecting Ethernet devices in a ring does not automatically establish redundancy.
For Siemens S7-1500 and ET 200 installations, Media Redundancy Protocol (MRP) requires compatible devices, correct ring-port configuration and appropriate manager and client roles. Commissioning should include a controlled recovery test rather than relying only on a green network status.
How MRP Maintains Network Availability
MRP is specified in IEC 62439-2. It enables a ring topology to provide an alternative transmission path when a link in the ring is interrupted.
One device acts as the redundancy manager, while other devices in the configured MRP domain act as clients. The manager supervises the ring and manages the path behavior when a break is detected.
Every device participating in the ring must support MRP, and the network topology must follow the manufacturer's configuration requirements.
Check Device Compatibility First
Before configuring the ring, verify the MRP capability of each switch, PLC interface—such as a Siemens S7-1500 CPU 1515-2 PN or Siemens S7-1500 CPU 1513-1 PN—and distributed I/O station such as the Siemens SIMATIC IM 155-6 PN interface module. A device that has two Ethernet ports is not necessarily an MRP-capable device.
Also check which physical ports are designated as ring ports. Siemens documentation identifies topology and port-role mismatches as configuration issues that can be detected during engineering or commissioning.
Configure the Ring in STEP 7
The Siemens configuration procedure includes the following main steps:
- Connect the devices as a line in the topology view.
- Connect the free end of the last device to the free end of the first device to create the ring.
- Select the PROFINET IO system in the network view.
- Open the MRP domain settings in the device or network properties.
- Assign the appropriate MRP role to each participating device.
- Verify the ring-port assignments and compile the configuration.
The exact menus and available options depend on the STEP 7 version and the participating device hardware.
Understand Ring Manager and Client Roles
A valid MRP domain needs an appropriate redundancy manager. Siemens documentation describes manager, manager-auto and client roles.
In a ring with a manager, the other participating devices use the client role. If no device is configured as a manager, at least one device must be configured as Manager (auto), subject to the supported device configuration.
Do not assign roles based only on the device's physical position in the cabinet. Check the supported role options in the device manual and the STEP 7 project.
Use Diagnostic Interrupts to Detect Ring Problems
Siemens MRP configuration documentation describes diagnostic interrupts for wiring or port errors, including:
- A neighboring device does not support MRP.
- An MRP ring port is connected to a non-ring port.
- A ring port is connected to a port belonging to another MRP domain.
- The ring is interrupted and subsequently restored.
Where configured, these events can be handled in the PLC program through the diagnostic error interrupt organization block OB 82.
Perform a Controlled Recovery Test
After configuration, perform a controlled test under an approved maintenance or commissioning plan.
- Record the normal network status and diagnostic buffer.
- Confirm that the ring is closed and the expected manager is active.
- Interrupt one designated ring link using the approved test procedure.
- Observe whether the network establishes the alternative path.
- Check PLC and device diagnostics for the ring interruption event.
- Restore the connection and confirm that the ring returns to its normal state.
Record the observed recovery behavior and compare it with the application requirements. Do not assume that MRP alone guarantees uninterrupted control or a specific recovery time for every device combination.
MRP Is Not the Same as System Redundancy
MRP provides network path redundancy. It does not automatically provide redundant PLC control, redundant I/O processing or application-level fault tolerance for connected field modules, such as a Siemens S7-1500 analog input module.
Those functions require separate hardware, software and system architecture considerations. The overall availability of a control system depends on more than the Ethernet ring.
Conclusion & Action Advice
A reliable PROFINET MRP ring requires compatible hardware, correct ring-port assignment, valid manager/client roles and verified diagnostics.
Include a controlled link-interruption test in commissioning and maintenance procedures so that redundancy is demonstrated, not merely assumed from the physical cabling.